TX7201 Addressable Zone Monitor unit is an addressable interface module, which will integrate conventional detectors or conventional manual call points to addressable system. When any of the connected devices alarms are active, the unit can send the alarm message to fire alarm controller, which generates alarm signal and displays its address. The unit can match with the conventional optical smoke detector, conventional rate of rise and fixed temperature detector and conventional manual call point etc. It has the function of checking short or open…
Price on request
Request a quotation
Confirm availability, delivery time and final order terms with our team.
TX7201 Addressable Zone Monitor unit is an addressable interface module, which will integrate conventional detectors or conventional manual call points to addressable system. When any of the connected devices alarms are active, the unit can send the alarm message to fire alarm controller, which generates alarm signal and displays its address. The unit can match with the conventional optical smoke detector, conventional rate of rise and fixed temperature detector and conventional manual call point etc. It has the function of checking short or open circuit of the output connection, by the End of Line Resistor (EOLR). The fault massage includes open circuit, short circuit or any removal of the detectors. The unit manufactured base on the requirement of EN 54 part 18, European Standard. The unit is aesthetically pleasing with unobtrusive design that will complement modern building designs and its plug-in type assembles make installation and maintenance more convenient to the installer. The unit is compatible to the TX7004 Analogue Intelligent Fire Alarm Control Panel, produced by single manufacture T&A, to avoid addressable communication compatibility problem.
EN54-18 Compliance Built-in MCU processor and digital addressing Intelligent self-diagnosis of open circuit Enhanced capacity of interference resistance by using multilevel wave filtering process LED status indicator Onsite Adjustable Parameter Loop and external power input Aesthetically pleasing design Parallel connecting up to 16 conventional detector Unit mounting with fix base for simple installation
Listed: LPCB Pending Compliance: EN54-18:2005/AC2007 Input Voltage: Loop Power:24VDC [16V to 28V] External PSU: 20 to 28VDC Current Consumption: Loop: Standby 1.3mA, Alarm: 5mA External PSU: Standby10mA, Alarm: 60mA Control output voltage: 24VDC (Only for the use of TX7130, do not allow the short circuit) End of line Resistance: 5.1Kohms/ ¼ W Protocol/ Addressing: T&A, Value range from 1 to 254 Indicator Status: Normal: Single blink/Active: Steady/Fault: Double Blink Material/Colour: ABS / White Glossy finishing Dimension/LWH: 108 mm x 86 mm x38 mm Weight: 154g(with Base),83g (without Base) Operating Temperature: -10°C to +50°C Ingress Protection Rating: IP30 Humidity: 0 to 95% Relative Humidity, Non condensing