Sensepoint XCD | Honeywell Fixed Gas Detector
Flammable, toxic and oxygen monitoring with tri-color display
The Honeywell Sensepoint XCD is a fixed gas detector used to monitor areas where flammable gases, toxic gases or oxygen deficiency may pose hazards to working environments. Detectors ship pre-configured with two programmable alarm relays, one programmable fault relay, a sink/source-selectable 4-20 mA output and Modbus communication. A tri-color backlit display shows status at a glance: steady green for normal operation, flashing yellow for fault and flashing red for alarm. It operates from 12-32 VDC across -40 C to +65 C ambient temperatures.
Brand: Honeywell · Category: Gas Detection
Key features
- Tri-color backlit status display
- Pre-configured out of the box
- Three sensor family options
- Non-intrusive magnetic operation
- Flameproof IP66 housing
Specifications
| Gas types | Flammable, toxic, oxygen |
|---|---|
| Input voltage | 12–32 VDC (24 VDC nominal) |
| Power consumption | 3.7 W (EC/IR), 4.9 W (catalytic) |
| Output | 4–20 mA (sink/source) + Modbus |
| Relays | 2 alarm + 1 fault, 5 A at 250 VAC |
| Operating temperature | -40 °C to +65 °C |
Contact Safety Shops for pricing, delivery and project support in the UAE.