MA-8000 | Honeywell Morley-IAS MAx Fire Alarm Control Panel
Multiprocessor addressable panel expandable to 8 loops
The Morley-IAS MAx MA-8000 is a multiprocessor addressable fire detection panel from Honeywell designed for the System Sensor and Morley-IAS protocols. In its basic configuration it provides 4 loops and can be expanded to 8 loops in the same box using two additional MA-LIB2 loop boards. Each loop delivers 750 mA and supports 99 detectors plus 99 input/output modules, and CAN-bus networking scales the system to 64 panels or 128 loops. Extended-capacity variants such as the MA-8000-04 support 127+127 devices per loop.
Brand: Honeywell · Category: Fire Alarm Systems
Key features
- Multiprocessor architecture
- In-cabinet loop expansion
- CAN-bus peer-to-peer networking
- High loop power for sounder devices
- Large graphical display
Specifications
| Loops | 4, expandable to 8 (MA-LIB2 boards) |
|---|---|
| Loop current | 750 mA per loop |
| Devices per loop | 99 detectors + 99 modules (127+127 extended) |
| Network capacity | 64 panels / 128 loops (CAN bus) |
| Protocol | System Sensor / Morley-IAS |
Contact Safety Shops for pricing, delivery and project support in the UAE.