SK-ZONE-6 | Honeywell Silent Knight 6-Zone Addressable Interface Module for FACPs
Silent Knight · Industrial Automation & Electrical
Description The Honeywell Silent Knight SK-ZONE-6 is an addressable six-zone interface module designed to connect conventional two-wire smoke detector zones to Silent Knight fire alarm control panels (FACPs). It transmits the zone status—normal, open, or alarm—to the control panel for monitoring and supervision. The SK-ZONE-6 provides dependable integration of legacy detection circuits into modern addressable fire alarm systems. Technical Specifications Condition New/Never Used Surplus Brand Silent Knight by Honeywell Category Fire Alarm Systems Part Number SK-ZONE-6 Subcategory Addressable Interface Modules Function Six-zone addressable interface for two-wire detectors Compatibility Silent Knight IntelliKnight Series FACPs Input Zones Six independent supervised inputs Wiring Type Class A or Class B SLC Loop Voltage 15–32 VDC External Power Supply 18–28 VDC, power-limited Standby Current 2 mA max Alarm Current 40 mA max (all six LEDs active) Initiating Device Circuit Resistance 25 Ω max Ripple Voltage 0.1 V RMS max LED Indicators One per zone input Addressing Method Rotary address switches Operating Temperature 32°F to 120°F (0°C to 48.9°C) Dimensions 6.8” H × 5.8” W × 1.0” D Mounting Options Dual module mounting in IDP-ACB cabinet Country of Origin United States Weight 0.4 lb (6.3 oz) Information About SK-ZONE-6 The SK-ZONE-6 is a six-input interface module that enables IntelliKnight and other Silent Knight Series FACPs to monitor conventional two-wire detector zones. Each input operates independently, sharing a common signaling line circuit (SLC) and external power source while maintaining full supervision. Designed for flexibility, the module supports both Class A and Class B wiring configurations and includes rotary address switches for simplified installation. The SK-ZONE-6 features LED indicators per zone input and allows disabling of up to two unused zones for optimized performance and system configuration. Key Features Six Independent Zone Inputs: Monitors up to six separate conventional detector circuits. SLC Integration: Converts traditional two-wire loops into addressable SLC circuits for Silent Knight FACPs. Full Supervision: Continuously monitors zone wiring, detectors, and external power supply for integrity. Flexible Wiring: Supports both Class A and Class B wiring for varied installation needs. Quick Installation: Rotary address switches simplify addressing and configuration. LED Indicators: Provides individual status indication for each input zone. Disable Option: Up to two unused inputs can be disabled when not required. Compact Mounting: Fits two modules per IDP-ACB cabinet with included hardware. The SK-ZONE-6 delivers the reliability and precision required for seamless integration of conventional detection zones into addressable fire alarm systems.
Brand: Silent Knight · Category: Industrial Automation & Electrical
Key features
- Six Independent Zone Inputs: Monitors up to six separate conventional detector circuits.
- SLC Integration: Converts traditional two-wire loops into addressable SLC circuits for Silent Knight FACPs.
- Full Supervision: Continuously monitors zone wiring, detectors, and external power supply for integrity.
- Flexible Wiring: Supports both Class A and Class B wiring for varied installation needs.
- Quick Installation: Rotary address switches simplify addressing and configuration.
- LED Indicators: Provides individual status indication for each input zone.
- Disable Option: Up to two unused inputs can be disabled when not required.
- Compact Mounting: Fits two modules per IDP-ACB cabinet with included hardware.
Specifications
| Manufacturer part number | SK-ZONE-6 |
|---|---|
| Condition | New/Never Used Surplus |
| Brand | Silent Knight by Honeywell |
| Category | Fire Alarm Systems |
| Part Number | SK-ZONE-6 |
| Subcategory | Addressable Interface Modules |
| Function | Six-zone addressable interface for two-wire detectors |
| Compatibility | Silent Knight IntelliKnight Series FACPs |
| Input Zones | Six independent supervised inputs |
| Wiring Type | Class A or Class B |
| SLC Loop Voltage | 15–32 VDC |
| External Power Supply | 18–28 VDC, power-limited |
| Standby Current | 2 mA max |
| Alarm Current | 40 mA max (all six LEDs active) |
| Initiating Device Circuit Resistance | 25 Ω max |
| Ripple Voltage | 0.1 V RMS max |
| LED Indicators | One per zone input |
| Addressing Method | Rotary address switches |
| Operating Temperature | 32°F to 120°F (0°C to 48.9°C) |
| Dimensions | 6.8” H × 5.8” W × 1.0” D |
| Mounting Options | Dual module mounting in IDP-ACB cabinet |
| Country of Origin | United States |
| Weight | 0.4 lb (6.3 oz) |
| Product type | Addressable Interface Modules |