S8600M1005 | Honeywell Universal Intermittent Pilot Ignition Control Module 24V AC
Honeywell · PLCs & Industrial Controllers
Description The Honeywell S8600M1005 is a universal intermittent pilot ignition control module designed for use with both natural and LP gas systems. It provides precise ignition sequencing, integrated pilot control, and continuous retry capability to ensure reliable burner operation in residential and commercial heating applications. Technical Specifications Condition New/Never Used Surplus Brand Honeywell Category HVAC Controls Part Number S8600M1005 Subcategory Ignition Control Modules Control Voltage 24V AC Lockout Time 15 sec (configurable to 90 sec) Pre-Purge Time 30 sec (configurable to none) Main Valve Current Output 2A max @165°F, 1A max @175°F Pilot Valve Current Output 1A Flame Sensor Current Output 1 μA Ignition Sequence Continuous retry after lockout Gas Type Natural or LP Flame Sense Type Single rod or two rods Ignition Source Internal high-voltage spark generator Compatible Gas Controls VR8204, VR8304 Compatible Ignition Hardware Q345, Q3451, Q3452 Ambient Operating Temperature -40°F to +165°F Frequency 50/60 Hz Dimensions (H x W x D) 3-15/16" x 5-7/16" x 2-5/8" Weight 0.50 lbs Information About S8600M1005 The S8600M1005 is part of Honeywell’s integrated ignition control solutions, offering compatibility with a wide range of gas control valves, including VR8204 and VR8304 models. Built with a durable enclosure, it supports both single-rod and two-rod flame sensing, and features an internal high-voltage spark generator for dependable ignition. The unit allows configurable pre-purge timing of 30 seconds or none, as well as adjustable lockout timing of 15 or 90 seconds to suit various system safety requirements. Designed for continuous retry ignition sequences, it helps maintain burner availability without compromising safety, making it a versatile replacement for many OEM ignition modules. Key Features: Universal Intermittent Pilot Ignition Control: Supports natural or LP gas systems with continuous retry capability for dependable burner operation. Adjustable Safety Timers: Configurable 15-second or 90-second lockout timing and optional 30-second pre-purge allow customization to system requirements. Integrated High-Voltage Spark Generator: Provides a strong and consistent ignition source to ensure quick pilot lighting under various conditions. Wide Flame Sensing Compatibility: Works with single-rod or two-rod flame sensors for flexible installation options. High Current Handling: Main valve current output rated at up to 2A at 165°F (1A at 175°F), with a pilot valve rating of 1A, ensuring compatibility with most gas valves. Robust Environmental Performance: Operates in ambient temperatures from -40°F to +165°F for year-round reliability. Multiple Ignition Hardware Options: Compatible with Q345, Q3451, and Q3452 hardware for easy field replacement. Compact Form Factor: Measures just 3-15/16" high x 5-7/16" wide x 2-5/8" deep for straightforward integration into existing control panels. Electrical Ratings: Operates at 24V AC, 50/60Hz, fitting standard control system power supplies. Precise Flame Detection: Flame sensor current output rated at 1 μA, ensuring accurate flame monitoring for safe operation. The S8600M1005 delivers the reliability and control precision required for safe and efficient ignition in modern heating systems.
Brand: Honeywell · Category: PLCs & Industrial Controllers
Key features
- Universal Intermittent Pilot Ignition Control: Supports natural or LP gas systems with continuous retry capability for dependable burner operation.
- Adjustable Safety Timers: Configurable 15-second or 90-second lockout timing and optional 30-second pre-purge allow customization to system requirements.
- Integrated High-Voltage Spark Generator: Provides a strong and consistent ignition source to ensure quick pilot lighting under various conditions.
- Wide Flame Sensing Compatibility: Works with single-rod or two-rod flame sensors for flexible installation options.
- High Current Handling: Main valve current output rated at up to 2A at 165°F (1A at 175°F), with a pilot valve rating of 1A, ensuring compatibility with most gas valves.
- Robust Environmental Performance: Operates in ambient temperatures from -40°F to +165°F for year-round reliability.
- Multiple Ignition Hardware Options: Compatible with Q345, Q3451, and Q3452 hardware for easy field replacement.
- Compact Form Factor: Measures just 3-15/16" high x 5-7/16" wide x 2-5/8" deep for straightforward integration into existing control panels.
- Electrical Ratings: Operates at 24V AC, 50/60Hz, fitting standard control system power supplies.
- Precise Flame Detection: Flame sensor current output rated at 1 μA, ensuring accurate flame monitoring for safe operation.
Specifications
| Manufacturer part number | S8600M1005 |
|---|---|
| Condition | New/Never Used Surplus |
| Brand | Honeywell |
| Category | HVAC Controls |
| Part Number | S8600M1005 |
| Subcategory | Ignition Control Modules |
| Control Voltage | 24V AC |
| Lockout Time | 15 sec (configurable to 90 sec) |
| Pre-Purge Time | 30 sec (configurable to none) |
| Main Valve Current Output | 2A max @165°F, 1A max @175°F |
| Pilot Valve Current Output | 1A |
| Flame Sensor Current Output | 1 μA |
| Ignition Sequence | Continuous retry after lockout |
| Gas Type | Natural or LP |
| Flame Sense Type | Single rod or two rods |
| Ignition Source | Internal high-voltage spark generator |
| Compatible Gas Controls | VR8204, VR8304 |
| Compatible Ignition Hardware | Q345, Q3451, Q3452 |
| Ambient Operating Temperature | -40°F to +165°F |
| Frequency | 50/60 Hz |
| Dimensions (H x W x D) | 3-15/16" x 5-7/16" x 2-5/8" |
| Weight | 0.50 lbs |
| Product type | Ignition Control Modules |