RM7895C1020 | Honeywell Flame Safeguard Burner Control 120 V Microprocessor Type

Honeywell · HVAC & Building Controls

RM7895C1020 | Honeywell Flame Safeguard Burner Control 120 V Microprocessor Type

Description  The Honeywell RM7895C1020 is a microprocessor-based primary burner control for automatically fired gas, oil, or combination-fuel burners. Operating on 120 Vac, it provides full burner management with interrupted pilot operation, flame supervision, and advanced safety sequencing for single-burner industrial applications.     Technical Specifications  Condition New/Never Used Surplus Brand Honeywell Category Burner Management Systems Part Number RM7895C1020 Subcategory Flame Safeguard Control Voltage 120 Vac (+10%, –15%) Frequency 50 Hz / 60 Hz (±10%) Control Type On-Off Primary with Pre-Purge Pilot Type Interrupted Flame Establishing Period (Pilot) 10 seconds Flame Establishing Period (Main) 10 seconds Ignition Cutout During Pilot Flame Establishing Period Pre-Purge Timing Determined by ST7800A Purge Timer Card Required Components Q7800A/B Subbase, R7847–R7861 Amplifier, ST7800A Card Indicators 5 LEDs for sequence and fault display Memory Type Nonvolatile – retains history and fault data Safety Timing Automatic lockout on flame failure Temperature Range (Storage/Shipping) –40 °F to +140 °F (–40 °C to +60 °C) Vibration Resistance 0.5 G Dimensions (with Subbase) 5 in W × 5 in H × 5¼ in D (Q7800A) / 6 ³⁄₃₂ in D (Q7800B) Approvals UL MP268, CSA LR95329-3, FCC Part 15 Class B, FM & CSD-1 accepted Weight 1 lb 15 oz (0.9 kg)     Information About RM7895C1020 The RM7895C1020 belongs to Honeywell’s 7800 Series of Flame Safeguard Controls, designed for reliable burner sequencing, flame detection, and system monitoring. This model functions as an On-Off primary control with pre-purge capability and is compatible with Q7800A/B subbases and ST7800A purge timer cards. It incorporates a solid-state microprocessor that governs all timing, safety interlocks, and diagnostic features while offering both local and remote indication through its LED array. The RM7895C1020 supports interchangeable plug-in flame amplifiers, selectable relight or lockout on flame loss, and nonvolatile memory for retaining fault history. Key Features: Microprocessor Control: Provides precise sequencing, flame supervision, and diagnostics for burner systems. Interrupted Pilot Operation: Controls pilot and main flame establishing periods independently (10 sec each). Selectable Flame Response: Offers relight or safety lockout modes upon loss of flame signal. Integrated LED Display: Five LEDs indicate system status, sequence position, and fault conditions. Pre-Purge Functionality: Pre-purge timing determined by the plug-in ST7800A purge timer card. Interchangeable Flame Amplifiers: Accepts multiple amplifier types for UV, rectification, or infrared sensing. Built-In Safety Logic: Provides ignition cutout during the pilot flame-establishing period for enhanced protection. Diagnostics and Data Retention: Nonvolatile memory stores operational history and status data. Modular Compatibility: Operates with Q7800A/B subbases and optional annunciators, display modules, and interfaces. Industry Certifications: UL recognized, CSA certified, and compliant with FCC Part 15 Class B emissions. The RM7895C1020 delivers the reliability and precision required for industrial burner management systems with automatic sequencing and advanced safety control.

Brand: Honeywell · Category: HVAC & Building Controls

Key features

Specifications

Manufacturer part numberRM7895C1020
ConditionNew/Never Used Surplus
BrandHoneywell
CategoryBurner Management Systems
Part NumberRM7895C1020
SubcategoryFlame Safeguard Control
Voltage120 Vac (+10%, –15%)
Frequency50 Hz / 60 Hz (±10%)
Control TypeOn-Off Primary with Pre-Purge
Pilot TypeInterrupted
Flame Establishing Period (Pilot)10 seconds
Flame Establishing Period (Main)10 seconds
Ignition CutoutDuring Pilot Flame Establishing Period
Pre-Purge TimingDetermined by ST7800A Purge Timer Card
Required ComponentsQ7800A/B Subbase, R7847–R7861 Amplifier, ST7800A Card
Indicators5 LEDs for sequence and fault display
Memory TypeNonvolatile – retains history and fault data
Safety TimingAutomatic lockout on flame failure
Temperature Range (Storage/Shipping)–40 °F to +140 °F (–40 °C to +60 °C)
Vibration Resistance0.5 G
Dimensions (with Subbase)5 in W × 5 in H × 5¼ in D (Q7800A) / 6 ³⁄₃₂ in D (Q7800B)
ApprovalsUL MP268, CSA LR95329-3, FCC Part 15 Class B, FM & CSD-1 accepted
Weight1 lb 15 oz (0.9 kg)
Product typeFlame Safeguard Control

Contact Safety Shops for pricing, delivery and project support in the UAE.