HS-NCM-W-2 | Notifier Network Communication Module
Notifier · Cables & Connectivity
Description The HS‑NCM‑W‑2 is part of Notifier’s High‑Speed Network Communications Module family, designed for seamless integration across Notifier fire alarm networks. Technical Specifications Condition New/Never Used Surplus Brand Notifier Category Fire Safety Part Number HS-NCM-W-2 Subcategory Fire Alarm Control Type High-Speed Network Communication Module Supported Medium Twisted-pair wire Network Operation Modes NFPA Style 4 (Class B) or NFPA Style 7 (Class A) Electrical Isolation Transformer coupling between nodes Wiring Connection Pluggable terminal wiring with strain relief Service Connector Pluggable bypass connector to pass signal through if power is removed from a node Transmission Rate 12 Mb Data Handling Data regenerated at each node Network Ports Two—simultaneous connection to fire alarm control panel and programming computer Software Support Enables software/database upload/download over High-Speed NOTI•FIRE•NET™ Max. Distance Between Nodes Up to 3,000 ft (914.4 m) point-to-point (varies with cable quality) Weight 0.65 lbs Information About HS-NCM-W-2 The HS-NCM-W-2 is part of Notifier’s high-speed network communication solutions, engineered to provide reliable, isolated, and high-capacity data transfer across fire alarm control networks. Designed for use with twisted-pair wiring, this module supports NFPA Style 4 (Class B) and Style 7 (Class A) network configurations, ensuring flexibility in system topology. Operating at a 12 Mb transmission rate with data regeneration at each node, the HS-NCM-W-2 enables seamless integration into NOTI•FIRE•NET™ networks for both new and expanded installations. With dual network ports, transformer-coupled isolation, and up to 3,000 ft between nodes, it delivers robust communication performance for complex fire protection systems. Key Features: Twisted-Pair Communication: Supports twisted-pair wire medium for versatile installation. Flexible Network Operation: Compatible with NFPA Style 4 (Class B) and Style 7 (Class A) wiring configurations. Electrical Isolation: Transformer coupling between nodes provides protection and signal integrity. Tool-Free Wiring: Pluggable terminal connections with strain relief for quick, secure installation. Service Connector: Passes network signal through even when module power is removed, maintaining communication integrity. High-Speed Transmission: Operates at 12 Mb with automatic data regeneration at each node for consistent performance. Dual Network Ports: Allows simultaneous connection to the fire alarm control panel and a programming computer. Programming Capability: Supports software/database upload and download over high-speed NOTI•FIRE•NET™. Long-Distance Support: Operates up to 3,000 ft (914.4 m) point-to-point, distance dependent on cable quality. Upgrade Path: Replaces the earlier HS-NCM-W model with enhanced speed and reliability. The Notifier HS-NCM-W-2 delivers high-speed, reliable, and isolated network communication for large or distributed fire alarm systems. With its flexible configuration options, long-distance capability, and robust performance, it is an ideal choice for mission-critical installations requiring fast and dependable system connectivity.
Brand: Notifier · Category: Cables & Connectivity
Key features
- Twisted-Pair Communication: Supports twisted-pair wire medium for versatile installation.
- Flexible Network Operation: Compatible with NFPA Style 4 (Class B) and Style 7 (Class A) wiring configurations.
- Electrical Isolation: Transformer coupling between nodes provides protection and signal integrity.
- Tool-Free Wiring: Pluggable terminal connections with strain relief for quick, secure installation.
- Service Connector: Passes network signal through even when module power is removed, maintaining communication integrity.
- High-Speed Transmission: Operates at 12 Mb with automatic data regeneration at each node for consistent performance.
- Dual Network Ports: Allows simultaneous connection to the fire alarm control panel and a programming computer.
- Programming Capability: Supports software/database upload and download over high-speed NOTI•FIRE•NET™.
- Long-Distance Support: Operates up to 3,000 ft (914.4 m) point-to-point, distance dependent on cable quality.
- Upgrade Path: Replaces the earlier HS-NCM-W model with enhanced speed and reliability.
Specifications
| Manufacturer part number | HS-NCM-W-2 |
|---|---|
| Condition | New/Never Used Surplus |
| Brand | Notifier |
| Category | Fire Safety |
| Part Number | HS-NCM-W-2 |
| Subcategory | Fire Alarm Control |
| Type | High-Speed Network Communication Module |
| Supported Medium | Twisted-pair wire |
| Network Operation Modes | NFPA Style 4 (Class B) or NFPA Style 7 (Class A) |
| Electrical Isolation | Transformer coupling between nodes |
| Wiring Connection | Pluggable terminal wiring with strain relief |
| Service Connector | Pluggable bypass connector to pass signal through if power is removed from a node |
| Transmission Rate | 12 Mb |
| Data Handling | Data regenerated at each node |
| Network Ports | Two—simultaneous connection to fire alarm control panel and programming computer |
| Software Support | Enables software/database upload/download over High-Speed NOTI•FIRE•NET™ |
| Max. Distance Between Nodes | Up to 3,000 ft (914.4 m) point-to-point (varies with cable quality) |
| Weight | 0.65 lbs |
| Product type | Network Communication Module |