ACPS-610 | Notifier Fire Alarm Power Supply
Notifier · Fire & Life Safety
Description The ACPS‑610 is an addressable auxiliary power supply and battery charger designed to enhance Notifier fire alarm systems. Technical Specifications Condition New/Never Used Surplus Brand Notifier Category Power Supply Systems Part Number ACPS-610 Subcategory Power Supplies Type Remote Power Supply / Charging Power Supply Output Capacity 6 A (with charging) or 10 A (with external charger) Mounting Options CAB-PS1, CAB-3, CAB-4, EQ Cabinet, BB-25, CHS-PS1 Programming PK-PPS Programming Utility (Windows® PC via USB cable) Primary (AC) Power PSE-6(C): 120 VAC, 50/60 Hz, 5.0 A maxACPS-610: 120 VAC, 50/60 Hz, 5.0 A maxACPS-610E: 220/240 VAC, 50/60 Hz, 2.5 A max Output Voltage 24 VDC regulated & power-limited (primary AC)20.4–26.4 VDC (secondary battery power) Output Circuits (TB3–TB6) NAC Output: 1.5 A max per circuitPower Output (battery charger disabled): 2.5 A max per circuit Battery Charging Circuit Supports 12–200 Ah lead-acid batteriesMax charger current: 5.0 A Secondary Power Auxiliary Outputs (TB2) 24 V @ 0.5 A (power-limited)5 V @ 0.15 A (power-limited) Wiring Size 12 to 18 AWG (3.1 to 0.78 mm²) SLC Specifications Avg. current: 1.287 mAData: 24.0 VDC / 5 VDC / 0 VDC @ ~3.33 Kbaud Battery Fuse (F2) 15 A, fast-acting Weight 4.5 lbs Information About ACPS-610 The ACPS-610 is part of Notifier’s line of intelligent fire alarm system accessories, designed to provide reliable auxiliary power and battery charging for demanding applications. This addressable charger/power supply module supports both CLIP and FlashScan® protocols, ensuring seamless integration with Notifier’s intelligent fire alarm control panels. Capable of delivering up to 6 A of shared power while charging batteries, or 10 A when using an external charger, the ACPS-610 combines high-capacity output with flexible configuration. With individually addressable outputs, built-in synchronization for major notification appliance brands, and comprehensive supervision features, it offers dependable performance for both new installations and system expansions. Key Features: High-Capacity Output: Provides 6 A total shared output with battery charging enabled, or 10 A when battery charging is disabled and an external charger is used. Configurable Outputs: Four individually addressable circuits, selectable as NACs, auxiliary power, four-wire detector power, or door-holder functions. NAC Synchronization: Built-in support for System Sensor®, Wheelock, and Gentex devices, with steady, March Time, Temporal, and UZC-coded output options. Battery Charging Capability: Charges 12–200 Ah lead-acid batteries with a maximum charge current of 5 A; supervised for faults and low voltage. Auxiliary Outputs: Includes 24 V @ 0.5 A and 5 V @ 0.15 A power-limited auxiliary outputs for peripheral devices. Power Reliability: Equipped with brown-out and surge protection circuitry for stable operation in challenging electrical environments. Comprehensive Supervision: Monitors AC loss, brown-out, battery faults, ground faults, open circuits, and output troubles. Programmable Interface: Configurable using the PK-PPS Windows® utility via USB connection for easy setup and customization. Flexible Mounting: Compatible with CAB-PS1, CAB-3, CAB-4, EQ cabinets, BB-25, and CHS-PS1 hardware. Standards Compliance: UL-listed, approved for seismic and marine applications when installed per manufacturer specifications. The Notifier ACPS-610 delivers robust, flexible auxiliary power and battery charging capabilities for intelligent fire alarm systems. With its high output capacity, programmable outputs, and built-in synchronization features, it is an ideal solution for complex installations requiring dependable and scalable power distribution.
Brand: Notifier · Category: Fire & Life Safety
Key features
- High-Capacity Output: Provides 6 A total shared output with battery charging enabled, or 10 A when battery charging is disabled and an external charger is used.
- Configurable Outputs: Four individually addressable circuits, selectable as NACs, auxiliary power, four-wire detector power, or door-holder functions.
- NAC Synchronization: Built-in support for System Sensor®, Wheelock, and Gentex devices, with steady, March Time, Temporal, and UZC-coded output options.
- Battery Charging Capability: Charges 12–200 Ah lead-acid batteries with a maximum charge current of 5 A; supervised for faults and low voltage.
- Auxiliary Outputs: Includes 24 V @ 0.5 A and 5 V @ 0.15 A power-limited auxiliary outputs for peripheral devices.
- Power Reliability: Equipped with brown-out and surge protection circuitry for stable operation in challenging electrical environments.
- Comprehensive Supervision: Monitors AC loss, brown-out, battery faults, ground faults, open circuits, and output troubles.
- Programmable Interface: Configurable using the PK-PPS Windows® utility via USB connection for easy setup and customization.
- Flexible Mounting: Compatible with CAB-PS1, CAB-3, CAB-4, EQ cabinets, BB-25, and CHS-PS1 hardware.
- Standards Compliance: UL-listed, approved for seismic and marine applications when installed per manufacturer specifications.
Specifications
| Manufacturer part number | ACPS-610 |
|---|---|
| Condition | New/Never Used Surplus |
| Brand | Notifier |
| Category | Power Supply Systems |
| Part Number | ACPS-610 |
| Subcategory | Power Supplies |
| Type | Remote Power Supply / Charging Power Supply |
| Output Capacity | 6 A (with charging) or 10 A (with external charger) |
| Mounting Options | CAB-PS1, CAB-3, CAB-4, EQ Cabinet, BB-25, CHS-PS1 |
| Programming | PK-PPS Programming Utility (Windows® PC via USB cable) |
| Primary (AC) Power | PSE-6(C): 120 VAC, 50/60 Hz, 5.0 A maxACPS-610: 120 VAC, 50/60 Hz, 5.0 A maxACPS-610E: 220/240 VAC, 50/60 Hz, 2.5 A max |
| Output Voltage | 24 VDC regulated & power-limited (primary AC)20.4–26.4 VDC (secondary battery power) |
| Output Circuits (TB3–TB6) | NAC Output: 1.5 A max per circuitPower Output (battery charger disabled): 2.5 A max per circuit |
| Battery Charging Circuit | Supports 12–200 Ah lead-acid batteriesMax charger current: 5.0 A |
| Secondary Power Auxiliary Outputs (TB2) | 24 V @ 0.5 A (power-limited)5 V @ 0.15 A (power-limited) |
| Wiring Size | 12 to 18 AWG (3.1 to 0.78 mm²) |
| SLC Specifications | Avg. current: 1.287 mAData: 24.0 VDC / 5 VDC / 0 VDC @ ~3.33 Kbaud |
| Battery Fuse (F2) | 15 A, fast-acting |
| Weight | 4.5 lbs |
| Product type | Fire Alarm Power Supply |