ECS-DUAL50W | Honeywell 100W Intelligent Voice Evacuation Amplifier
Farenhyt · Industrial Automation & Electrical
Description The Honeywell ECS-DUAL50W is an intelligent 50/100-watt voice evacuation amplifier designed for emergency communication systems. It delivers up to 100 watts of audio power at 25 VRMS or 70.7 VRMS across dual 50-watt circuits. Engineered for integration with Honeywell ECS panels, it supports supervised voice messaging and life safety notification applications. Technical Specifications Condition New/Never Used Surplus Brand Honeywell Category Fire Alarm Systems Part Number ECS-DUAL50W Subcategory Voice Evacuation Amplifiers Total Output Power 100 W @ 25 VRMS or 70.7 VRMS Circuit Capacity Circuits 1–4: 50 W Max; Circuits 5–8: 50 W Max Primary AC Input 120 VAC @ 60 Hz; 240 VAC @ 50 Hz Standby Current 110 mA (25V & 70.7V) Alarm Current 1.2 A @ 25V; 1.4 A @ 70.7V SBUS Standby & Alarm 10 mA Battery Charging Capacity 7–35 AH Max Battery in Cabinet 18 AH (Use RBB for up to 35 AH) Voice Integration Wiring Six Conductor (2 Voice Bus, 4 SBUS) Operating Temperature 32°F – 120°F (0°C – 49°C) Operating Humidity 10% – 93% Non-Condensing Flush Mount Dimensions 14.5”W x 24.75”H x 3.4”D Overall Dimensions 16.1”W x 26.5”H x 4.125”D Color Red Approvals UL 864, UL 2572, UL 1711; NFPA 13, 70, 72 Weight 30 lb Information About ECS-DUAL50W The ECS-DUAL50W is a Honeywell intelligent amplifier developed for use within Emergency Communication Systems (ECS) requiring distributed voice evacuation capability. It provides a total of 100 watts output, divided between circuits 1–4 and 5–8 at 50 watts maximum per group. Designed for compatibility with Honeywell ECS panels via SBUS and voice bus wiring, it supports six-conductor integration for system communication and supervision. The unit operates on 120 VAC @ 60 Hz or 240 VAC @ 50 Hz and includes onboard battery charging capacity for standby power support. Key Features: Dual 50-Watt Amplification: Provides up to 100 W total output at 25 VRMS or 70.7 VRMS. Multi-Circuit Distribution: Circuits 1–4 and 5–8 support up to 50 W each grouping. Voice Evacuation Integration: Designed for ECS voice notification systems. SBUS & Voice Bus Connectivity: Six-conductor wiring (two voice bus, four SBUS) for panel communication. Battery Charging Capability: Supports 7–35 AH batteries (18 AH max in cabinet). Wide Voltage Input: Operates on 120 VAC @ 60 Hz or 240 VAC @ 50 Hz. UL & NFPA Compliant: Meets UL 864, UL 2572, UL 1711 and NFPA 13, 70, 72 standards. Industrial Enclosure: Red cabinet suitable for fire alarm and ECS installations. The ECS-DUAL50W delivers the reliability and precision required for supervised voice evacuation and emergency communication systems in commercial facilities.
Brand: Farenhyt · Category: Industrial Automation & Electrical
Key features
- Dual 50-Watt Amplification: Provides up to 100 W total output at 25 VRMS or 70.7 VRMS.
- Multi-Circuit Distribution: Circuits 1–4 and 5–8 support up to 50 W each grouping.
- Voice Evacuation Integration: Designed for ECS voice notification systems.
- SBUS & Voice Bus Connectivity: Six-conductor wiring (two voice bus, four SBUS) for panel communication.
- Battery Charging Capability: Supports 7–35 AH batteries (18 AH max in cabinet).
- Wide Voltage Input: Operates on 120 VAC @ 60 Hz or 240 VAC @ 50 Hz.
- UL & NFPA Compliant: Meets UL 864, UL 2572, UL 1711 and NFPA 13, 70, 72 standards.
- Industrial Enclosure: Red cabinet suitable for fire alarm and ECS installations.
Specifications
| Manufacturer part number | ECS-DUAL50W |
|---|---|
| Condition | New/Never Used Surplus |
| Brand | Honeywell |
| Category | Fire Alarm Systems |
| Part Number | ECS-DUAL50W |
| Subcategory | Voice Evacuation Amplifiers |
| Total Output Power | 100 W @ 25 VRMS or 70.7 VRMS |
| Circuit Capacity | Circuits 1–4: 50 W Max; Circuits 5–8: 50 W Max |
| Primary AC Input | 120 VAC @ 60 Hz; 240 VAC @ 50 Hz |
| Standby Current | 110 mA (25V & 70.7V) |
| Alarm Current | 1.2 A @ 25V; 1.4 A @ 70.7V |
| SBUS Standby & Alarm | 10 mA |
| Battery Charging Capacity | 7–35 AH |
| Max Battery in Cabinet | 18 AH (Use RBB for up to 35 AH) |
| Voice Integration Wiring | Six Conductor (2 Voice Bus, 4 SBUS) |
| Operating Temperature | 32°F – 120°F (0°C – 49°C) |
| Operating Humidity | 10% – 93% Non-Condensing |
| Flush Mount Dimensions | 14.5”W x 24.75”H x 3.4”D |
| Overall Dimensions | 16.1”W x 26.5”H x 4.125”D |
| Color | Red |
| Approvals | UL 864, UL 2572, UL 1711; NFPA 13, 70, 72 |
| Weight | 30 lb |
| Product type | Voice Evacuation Amplifiers |
Contact Safety Shops for pricing, delivery and project support in the UAE.