Description  The Beckhoff EL3413 is a 3-channel EtherCAT analog input terminal for power measurement applications supporting voltages up to 690 V AC and currents up to 5 A. It provides precise 16-bit resolution measurements for voltage, current, power, energy, and frequency, making it suitable for high-performance industrial and renewable energy monitoring.   Technical Specifications  Condition New/Never Used Surplus Brand Beckhoff Category Industrial Automation Part Number EL3413 Subcategory EtherCAT Power Measurement Terminal Technology 3-phase power measurement for alternating voltages Number of Inputs 4 × current, 3 × voltage Signal Type Single-ended Measuring Voltage Max. 690 V AC 3~ (ULX-N: max. 400 V AC) Measuring Current Adjustable: 100 mA AC, 1 A AC (default), 5 A AC; potential-free Resolution 16-bit (1 μA, 0.1 mV, 10 mW) Measured Values Current (I1, I2, I3, In), voltage, active/reactive/apparent power, energy, cos φ, frequency, harmonics Measurement Error/Uncertainty 0.5% (U/I full scale), 1% (calculated value) Electrical Isolation 4500 V Conversion Time Mains-synchronous Special Features Galvanically isolated current inputs, harmonic analysis, optional single-phase operation Current Consumption (E-Bus) Typ. 160 mA Protection Rating IP20 Operating Temperature -25°C to +60°C Storage Temperature -40°C to +85°C Relative Humidity 95%, non-condensing Vibration/Shock Resistance EN 60068-2-6 / EN 60068-2-27 compliant EMC Compliance EN 61000-6-2 / EN 61000-6-4 Approvals CE Dimensions (W × H × D) 24 mm × 100 mm × 68 mm Weight 0.20 lbs (approx. 100 g)   Information About EL3413 The EL3413 is part of Beckhoff’s EtherCAT I/O series and serves as an advanced 3-phase power measurement terminal designed for direct connection to high-performance generators and electrical systems. Supporting up to 690 V AC, it eliminates the need for upstream voltage transformers, simplifying system integration in power distribution and renewable energy applications. Its galvanically isolated current inputs allow safe and flexible use with 2- or 3-transformer configurations, including star and delta systems. The terminal provides detailed power analysis, including active, reactive, and apparent power, energy values, and harmonic analysis up to the 21st harmonic, all available through process data. Key Features: High-Voltage Capability: Measures voltages up to 690 V AC directly, removing the need for external voltage transformers. Flexible Current Range: Adjustable current inputs (100 mA to 5 A) with galvanic isolation for versatile system configurations. Comprehensive Power Analysis: Delivers accurate measurement of voltage, current, power, energy, and frequency values in real time. Harmonic Analysis: Supports harmonic content analysis up to the 21st order for network quality assessment. Precision and Stability: Provides 16-bit measurement resolution with only 0.5% error relative to full-scale readings. Safe and Reliable Design: Features 4500 V isolation and CE certification for safe use in industrial and energy environments. Direct Generator Monitoring: Optimized for high-performance generator applications such as those in the wind energy sector. Compact and Durable Form Factor: Built to withstand harsh environmental conditions with IP20 protection and -25°C to +60°C operating range. The EL3413 delivers the reliability and precision required for industrial power monitoring, energy management, and harmonic analysis in advanced automation systems.

Brand: Beckhoff · Category: Cables & Connectivity

Key features

Specifications

Manufacturer part numberEL3413
ConditionNew/Never Used Surplus
BrandBeckhoff
CategoryIndustrial Automation
Part NumberEL3413
SubcategoryEtherCAT Power Measurement Terminal
Technology3-phase power measurement for alternating voltages
Number of Inputs4 × current, 3 × voltage
Signal TypeSingle-ended
Measuring VoltageMax. 690 V AC 3~ (ULX-N: max. 400 V AC)
Measuring CurrentAdjustable: 100 mA AC, 1 A AC (default), 5 A AC; potential-free
Resolution16-bit (1 μA, 0.1 mV, 10 mW)
Measured ValuesCurrent (I1, I2, I3, In), voltage, active/reactive/apparent power, energy, cos φ, frequency, harmonics
Measurement Error/Uncertainty0.5% (U/I full scale), 1% (calculated value)
Electrical Isolation4500 V
Conversion TimeMains-synchronous
Special FeaturesGalvanically isolated current inputs, harmonic analysis, optional single-phase operation
Current Consumption (E-Bus)Typ. 160 mA
Protection RatingIP20
Operating Temperature-25°C to +60°C
Storage Temperature-40°C to +85°C
Relative Humidity95%, non-condensing
Vibration/Shock ResistanceEN 60068-2-6 / EN 60068-2-27 compliant
EMC ComplianceEN 61000-6-2 / EN 61000-6-4
ApprovalsCE
Dimensions (W × H × D)24 mm × 100 mm × 68 mm
Weight0.20 lbs (approx. 100 g)
Product typeEtherCAT Power Measurement Terminal